Switchgears

Updated: Oct 25, 2023

Working Principle of Switchgears:


Switchgear is an electrical apparatus used to control, protect, and isolate electrical circuits and equipment. It operates on the principle of interrupting or isolating the flow of electrical current under normal and abnormal conditions. The primary function of switchgear is to ensure the safety and reliability of electrical power systems.

 

Construction Parts & Purpose:


1. Circuit Breaker: It is the main component of switchgear used to interrupt the current flow during fault conditions.

2. Busbars: These conductors serve as a common electrical junction, connecting various devices within the switchgear.

3. Disconnect Switches: They provide a means to isolate circuit breakers or other devices for maintenance or repair.

4. Fuses: These protective devices are used to interrupt the current flow in case of overloads or short circuits.

5. Instrument Transformers: Current transformers and voltage transformers are used to measure current and voltage levels for protection and metering purposes.

6. Relays: They monitor electrical parameters and initiate circuit breaker operation in case of abnormal conditions, such as overcurrent, undervoltage, or overvoltage.

 

Different Types of Switchgears:


1. Low Voltage (LV) Switchgear: Used in residential, commercial, and small industrial applications with voltage levels up to 1000V.

2. Medium Voltage (MV) Switchgear: Designed for medium-sized industrial applications and power distribution networks with voltage levels between 1 kV and 33 kV.

3. High Voltage (HV) Switchgear: Used in large power systems and substations with voltage levels above 33 kV.

 

Typical Ratings Used in India:


In India, switchgear ratings vary depending on the specific application. For LV switchgear, typical ratings can range from 415V to 1000V, while MV switchgear ratings can range from 3.3 kV to 33 kV. HV switchgear ratings are generally above 33 kV.

 

Protection System & Typical Settings:


Switchgear incorporates various protection systems to safeguard electrical equipment. Typical settings depend on the specific application, but common protection schemes include overcurrent, short circuit, earth fault, differential, and distance protection. Settings are determined based on the characteristics of the electrical system and equipment being protected.

 

Preventive Maintenance:


Preventive maintenance is crucial to ensure the reliability and longevity of switchgear. It includes regular inspection, cleaning, lubrication, and testing of switchgear components. Maintenance schedules should be followed as per manufacturer recommendations and local regulations.

 

Different Testing, method and reasoning


1. Insulation Resistance Test:


Procedure:

- Disconnect all power sources and discharge any stored energy.

- Apply a DC voltage (usually 500V or 1000V) between all live conductors and earth.

- Measure the insulation resistance using a megohmmeter.


Reference Result Value: The recommended minimum insulation resistance value is typically 1 megohm for LV switchgear and 1 gigohm for MV/HV switchgear.


If Result Fails:

- Probable Reasons: Moisture or contamination on the insulation, insulation aging or degradation, damaged insulation due to mechanical stress or overheating.


2. Dielectric Test (High Voltage Withstand Test):


Procedure:

- Apply a high voltage (usually above rated voltage) between different live parts and earth for a specified duration.

- Monitor the leakage current and check for any breakdown or flashovers.

Reference Result Value: The switchgear should withstand the applied voltage without any flashovers or excessive leakage current.


If Result Fails:

- Probable Reasons: Insufficient insulation, presence of moisture or contaminants, insulation breakdown or aging.


3. Contact Resistance Test:


Procedure:

- Isolate the switchgear from the power source and discharge any stored energy.

- Measure the resistance between different contact points using a low-resistance ohmmeter.


Reference Result Value: The contact resistance value should be within the manufacturer's specified limits, typically in milliohms.


If Result Fails:

- Probable Reasons: Loose or corroded connections, damaged or worn-out contacts, improper assembly or alignment.


4. Operation Test:


Procedure:

- Simulate various operating conditions such as normal switching, fault conditions, and emergency shutdowns.

- Verify that all control mechanisms, including circuit breakers, relays, and interlocks, operate correctly.

Reference Result Value: The switchgear should operate as intended without any abnormal behavior or failures.


If Result Fails:

- Probable Reasons: Mechanical wear and tear, malfunctioning control mechanisms, faulty wiring or connections.


5. Short-Circuit Test:


Procedure:

- Simulate a short-circuit condition by applying a high-current fault to the switchgear.

- Monitor the performance of protective devices such as circuit breakers, fuses, or relays.


Reference Result Value: The protective devices should operate within the specified time and interrupt the fault current effectively.


If Result Fails:

- Probable Reasons: Faulty or misadjusted protective devices, inadequate fault current interrupting capacity, improper coordination of protective devices.


6. Temperature Rise Test:


Procedure:

- Apply a rated load to the switchgear for a specific duration.

- Monitor the temperature rise of various components, such as conductors, contacts, and insulation.

Reference Result Value: The temperature rise should not exceed the manufacturer's specified limits to ensure safe operation.


If Result Fails:

- Probable Reasons: Inadequate cooling, overloaded components, poor thermal dissipation, defective cooling systems.

 

Fault Scenarios, Causes, Effects, and Remedies:

Fault scenarios in switchgear can occur due to various reasons, such as short circuits, overloads, insulation failures, or equipment malfunctions. The causes can include human error, equipment aging, environmental factors, or manufacturing defects. The effects of faults can range from power interruptions to equipment damage or even electrical hazards. Remedies involve prompt fault detection, isolation of faulty components, and restoration of normal operations. This may include replacing damaged equipment, resetting circuit breakers, or repairing insulation faults. Proper fault analysis and investigation help prevent future occurrences.